Undetected Loss of Prime Mover
A steam turbine at a distributed generation site, operating in parallel with the utility grid, suddenly lost its prime mover, the steam supply. The existing electromechanical protection failed to recognize the
motoring condition, which resulted in the generator operating as a synchronous motor for an extended period of time. The thermal turbine scheme of the generator also failed to detect the motoring condition. Finally,
an operator noticed the real power output at nearly zero and manually tripped the breaker between the industrial electric power system and the utility
The BE1-GPS100 provided dramatically improved reverse power protection, performance of the 32R function is an order of magnitude better than the existing previous-technology relays.
For details, see Application Note PC-GPS01 - Loss of Prime Mover: Generator Reverse Power Protection (32) Replacement Opportunities (GE Type
GGP-53C and ABB Type CW)
|