Visit the Basler web site Basler Electric Basler Electric Jobs at Basler Site Map
Link to Home Link to Company Info Link to Products Link to Newsletter Information/Support
Protection and Control Systems Spacer Regulation and Systems Control Spacer Static Excitation Systems Spacer Magnetic Product Group Spacer Request for Quote Link

Easy Setup with Logic Files for BE1-11

Intertie Protection


BE1-11 Logic Library

Click to see larger image

Where BESTCOMSPlus® makes it easy to set relays, BESTspace makes it easy to configure BESTCOMSPlus and utliize BESTLogicPlus. The BESTspace tool in BESTCOMSPlus allows you to clearly identify relevant settings and adapt them to your specific application - minimizing errors and time spent creating settings files. The files below will assist you in using Basler Electric preconfigured BESTspace and preprogrammed BESTLogicPlus logic files.

BESTLogicPlus programmable logic provides the user with a highly flexible and easy to use visual method of configuring a protection and control system in the BE1-11 family of products. It comes standard with each BE1-11 family relay.

Click on the label (left and right) to see the logic file description, then scrolldown and use the button on the right to download and Application Note about the logic scheme and BESTSpace file, a PDF of the logic diagram, or the actual logic file.

Note: To use logic, you must have
BESTCOMSPlus® installed.

Download the Application Note PC-BESTSPACE - to learn how to use the BESTCOMSPlus® BESTspace™ feature to easily set your relay

Basic Low Impedance Grounded Generator Protection

Basic Overcurrent Protection

Basic High Impedance Grounded Generator Protection

Overcurrent Protection with Control Low Impedance Grounded Generator Protection with Sequential Trip
Overcurrent Protection with Reclosing High Impedance Grounded Generator Protection with Sequential Trip
Feeder Protection
with Interlock
Low Impedance Grounded Generator Protection with Sequential Trip and Sync-Check

Primary Bus Overcurrent Protection

Backup Bus Overcurrent Protection

Intertie Protection Scheme - BE1-11i

 
Updated! Intertie Protection - Provides protection elements to cover all intertie needs defined by IEEE Standard 1547-2003. The logic scheme is comprised of two phase, ground and negative sequence directional instantaneous overcurrent zones, and two phase and ground, and one negative sequence directional time overcurrent zones. Network and conditional reclosing (25 and 25VM), breaker failure protection, over/under voltage phase protection, directional power, and over/under/rate of change frequency protection are included in this scheme. This scheme can be used in conjunction with other Basler Electric products to provide main-to-main protection. May be used with BE1-11i and BE1-11g relays.

Application Note

BESTspace file

Print Out

Logic File


Feeder Protection Schemes - BE-11f


Updated! Basic Overcurrent Protection
- Provides basic time and instantaneous overcurrent protection. Included protective elements are phase, neutral, and negative-sequence overcurrent protection. Functions such as breaker failure, virtual breaker control, automatic reclosing, and protective voltage features are not enabled in this scheme. However, these features may be activated through BESTLogicPlus.

Application Note

BESTspace file

Print Out

Logic File


Updated! Overcurrent Protection with Control -
Similar to Overcurrent Protection with Reclosing but has the added ability to manually open and close the breaker by using the virtual breaker control switch (101). Breaker failure and voltage protection features are not included in this scheme. However, these features may be activated through BESTLogicPlus.

Application Note

BESTspace file

Print Out

Logic File



Updated! Overcurrent Protection with Reclosing
- Provides time and both high-set and low-set instantaneous overcurrent elements for phase, neutral, and negative-sequence protection. Automatic reclosing is included and initiated (RI) by a protective trip or by an external reclose initiate contact. Breaker failure, virtual breaker control, and protective voltage features are not activated in this scheme. However, these features may be activated through BESTLogicPlus.



Application Note

BESTspace file

Print Out

Logic File


Updated! Feeder Protection with Interlock
- Provides time and both high-set and low-set instantaneous overcurrent elements for phase, neutral and negative-sequence protection. Automatic reclosing is included and initiated (RI) by a protective trip. The breaker may be manually opened or closed via the virtual breaker control switch (101). Protective voltage features are not enabled in this scheme. However, these features may be activated through BESTLogicPlus. Interlock logic allows for bus overcurrent backup of feeder relays and allows for fast bus overcurrent protection.

Application Note

BESTspace file

Print Out

Logic File


Updated! Primary Bus Overcurrent Protection -
Applies to a bus main relay to provide primary bus overcurrent protection. Contains logic to interconnect with the Feeder Protection with Interlock logic scheme to provide high-speed overcurrent protection for the bus under normal conditions. It also contains logic to trip the feeder breakers while the feeder relays using the Feeder Protection with Interlock logic scheme are out of service.

Application Note

BESTspace file

Print Out

Logic File


Updated! Backup Bus Overcurrent Protection
- Apply to a bus main relay to provide backup bus overcurrent protection as well as breaker failure protection for the bus breaker under normal conditions. Also provides primary bus overcurrent protection when the relay using the Primary Bus Overcurrent Protection logic scheme is providing feeder protection or when the primary bus relay is out of service.

Application Note

BESTspace file

Print Out

Logic File


Generator Protection Schemes - BE1-11g

Updated! Basic Low Impedance Grounded Generator Protection - Provides basic protection of generators grounded through a low to moderate neutral impedance. The simple and straightforward tripping scheme provides for three tripping outputs using the same logic for all three outputs. Tripping functions include 24, 27 Phase, two 32 Reverse Power, 40Q, 40Z, 46, 47, 50P/50N Inadvertent Energizing, 51 Phase with voltage control, 51 Neutral(calculated 3I0), 51 Ground, 59 Phase, two 81 under, two 81 over. Does not provide for sequential trip logic or synchronism check.

Application Note

BESTspace file

Print Out

Logic File


Updated! Basic High Impedance Grounded Generator Protection
- Provides basic protection of generators grounded through a high neutral impedance. The simple and straightforward tripping scheme provides for three tripping outputs with the same logic being used for all three outputs. Tripping functions include 24, 27 Phase, 27 Neutral (third harmonic), two 32 Reverse Power, 40Q, 40Z, 46, 47, 50P/50N Inadvertent Energizing, 51 Phase with voltage control, 51 Neutral (calculated 3I0), 51 Ground, 59 Phase, 59 Neutral, 59 Neutral (calculated 3V0), two 81 under, two 81 over. Does not provide for sequential trip logic or synchronism check.


Application Note

BESTspace file

Print Out

Logic File


Updated! Low Impedance Grounded Generator Protection with Sequential Trip -
Provides for more elaborate protection for generators grounded through a low to moderate neutral impedance. This scheme’s logic offers more features, as compared to the basic low impedance logic. It adds sequential trip logic and implements a more involved tripping scheme. It provides three trip output contacts: one each for main breaker, field, and prime mover tripping, with different logic for each. As in the basic low impedance logic, tripping, functions include 24, 27 Phase, two 32 Reverse Power, 40Q, 40Z, 46, 47, 50P/50N Inadvertent Energizing, 51 Phase with voltage control, 51 Neutral (calculated 3I0), 51 Ground, 59 Phase, two 81 under, two 81 over, except there is selective and intertied logic that discriminates on which output each function trips. It provides for sequential trip logic, but not synchronism check.


Application Note

BESTspace file

Print Out

Logic File


Updated! High Impedance Grounded Generator Protection with Sequential Trip
- Provides for more elaborate protection for generators grounded through high neutral impedance. This scheme’s logic offers more features, as compared to the basic high impedance logic. It adds sequential trip logic and implements a more involved tripping scheme. It provides three trip output contacts: one each for main breaker, field, and prime mover tripping, with different logic foreach. As in the basic high impedance logic, functions include 24, 27 Phase, 27 Neutral(third harmonic), two 32 Reverse Power, 40Q, 40Z, 46, 47, 50P/50N Inadvertent Energizing, 51 Phase with voltage control, 51 Neutral (calculated 3I0), 51 Ground, 59 Phase, 59 Neutral, 59 Neutral (calculated 3V0), two 81 under, two 81 over, except there is selective and intertied logic that discriminates on which output each function trips. It provides for sequential trip logic, but not synchronism check.

Application Note

BESTspace file

Print Out

Logic File


Updated! Low Impedance Grounded Generator Protection with Sequential Trip and Sync-Check
- Provides for more elaborate protection for generators grounded through a low to moderate neutral impedance. This scheme’s logic offers more features, as compared to the basic low impedance logic. It adds sequential trip logic, sync-check, and implements a more involved tripping scheme. It provides three trip output contacts: one each for main breaker, field, and prime mover tripping, with different logic for each and breaker close output that can be used for sync-check or dead bus close. As in the basic low impedance logic, functions include 24, 27 Phase, two 32 Reverse Power, 40Q, 40Z, 46, 47, 50P/50N Inadvertent Energizing, 51 Phase with voltage control, 51 Neutral (calculated 3I0), 51 Ground, 59 Phase, two 81 under, two 81 over, except there is selective and intertied logic that discriminates on which output each function trips. It provides for sequential trip logic and synchronism check.


Application Note

BESTspace file

Print Out

Logic File


Top | Welcome | Basler Electric - The Company | Exciters | Gen Controls | Regulators | Relays | Transformers |
News | Employment | Support | Site Map | Basler Phone, Fax and Address | Privacy Policy
 

© Copyright Basler Electric Company - All Rights Reserved