BE1 Numerical Protection Systems are available in rack mount or retrofit friendly packages for any application. Their BESTlogic programmable logic provides the user with flexibility, while common protocols aid integration. Click here to see communications capabilities for the entire line.

Divider Line


BE1-CDS240
Current Differential Protection System with Voltage
 

Product Bulletin

Instruction Manual

Protocol Manuals

Product Software

Application Guides

Guideform Specifications

Bulletin UHT (includes stylechart)

BE1-CDS240 Manual

DNP3 manual

BESTCOMS

Generator Protection

BE1-CDS240 Specs in Word

 

BE1-CDS240
Manual by sections

Modbus Manual

BESTwave

Transformer Protection

BE1-CDS240 Specs in PDF

 

 

 

BESTprint

 

 

Click here for Application Notes and Technical Papers and other Resources

The BE1-CDS240 Current Differential Protection System is a 3 phase multifunction numerical relay that provides percentage restrained differential protection along with overcurrent, voltage, frequency, breaker failure, control, metering, monitoring, and alarm functions in an integrated system. The BE1-CDS240 Current Differential Protection System is available with 2, 3, or 4 sets of low impedance 3 phase restraint inputs.

All configurations include one set of 3 phase voltage inputs and an independent ground input for earth fault and ground differential (Restricted Earth Fault, 87ND).

BE1-CDS240
The CDS240 is available in horizontal and vertical configurations to provide cost savings in any installation.
Protective Relays
Application Table
Application Engineers
Regional Sales Managers
Sales Reps
Previous page Next Page


Device Functions

24

50

BF

81

27

51

60

87

47

59

62

DNP
Option

Modbus
RTU
Option


All versions include harmonic restraint as well as phase shift and tap compensation for use in transformer applications. Detailed differential check report provides confirmation of proper CT connections.

Features include:

  • Up to 4 sets of 3 phase current inputs, plus standard 3 phase voltage and independent ground inputs provide complete protection and metering for 2 to 4 terminal differential applications.
  • 10 to 14 contact outputs and 8 to 12 contact inputs, all BESTlogic programmable, plus a dedicated alarm output.
  • "Virtual Circuits" allow internal summing of 2 or 3 sets of currents for use in protection and metering.
  • Non-volatile storage of all target, oscillography, fault records, and SER data.
  • Variable sample rate for frequency tracking allows for high accuracy in generator and motor differential applications.
  • BESTlogic provides the user with complete flexibility in configuring a protection and control system. User programmable variable and switch names make the CDS240 relays completely self-documenting.
  • Each CT circuit is low burden and isolated to allow improving zones of protection with fewer costly CTs.
  • Large Bit Addressable LCD display allows the relay to replace local indication and control functions such as panel metering, alarm annunciation, and control switches.
  • Expansion slot for communications coprocessor module provides a future upgrade path for Ethernet, IEC 61850, and other high-speed protocols.
  • Three independent communications ports allow integration with distributed control systems, modems, and fixed or portable PCs. DNP protocol is available as an option. Consult factory for availability of Modbus™ protocol.
  • Current circuits not used for differential protection can be used for independent overcurrent protection functions.
  • The CDS240 uses a drawout module with automatic CT shorting facilities and fits cutout and drilling dimensions for many common Basler Electric, GE (BDD), and Westinghouse (HU) differential relays.
  • BESTCOMS GUI software available to aid in setup.
     

Application Notes and Technical Papers and other Resources

Application Notes
- Application Note PC-COM01 - Basic instructions for setting up HyperTerminal and Terminal
- Application Note PC_RTF Compare - Instructions for an easy way to quickly and accurately compare two numeric relay settings files using BESTCOMS and Microsoft® Word.
- Application Note PC-ArcFlash - Arc Flash Hazard Mitigation Through Relaying
- Application Note PC-CDS04 - Numeric multifunction relays fit in existing panel cutouts for transformer differential and overcurrent relays, upgrading existing protection without the need for large scale capital projects, saving time and money.

Technical Papers
- Using Iop Characteristics to Troubleshoot Transformer Differential Relay Misoperation
- Reliability Considerations of Multifunction Protection
- Ground Differential Protection: Revisited
- Breaker Monitoring with Numerical Relay
- Commissioning Numerical Relays
- Unconventional Connections and How to Get It Right
 - Predicting Current Differential Relay Tripping and Targeting when Testing at Final Settings

Other Resources
- BNS Time Current Characteristic Spreadsheet
- Electric Calculations Spreadsheet
- Transformer Differential Calculations